Fluke 1630 Earth Ground Clamp Meter
Mã Số: 
Giá Bán: Contacts us

 

Fluke 1630 Earth Ground Clamp Meter


Provider: Fluke
Category: Fluke-Test tools / Earth Ground Testers
Price: Call us (84-8) 39 572 812
 

  • A wide ground loop resistance range, from 0.025 Ω to1500 Ω, to satisfy all requirements
  • Large jaw opening of 35 mm (1.38 in) for tests on ground conductors and/or equipotential bus bars
  • Measurement of ground leakage current, from 0.2 mA to 1000 mA, without needing to disconnect - ideal for system troubleshooting
  • Wide ac current measurement range from 0.2 A to 30 A allows one instrument for multiple applications
  • User-defined HI / LO Alarm limits, for rapid measurement evaluation
  • Handy ‘display hold’ button for capturing readings in hard-to-reach places
  • Time saving memory function automatically records and stores measured values
  • Automatic self calibration ensures correct measurement every time
  • Overload protection: 200 A
  • Carrying case and resistance test loop included
  • ≥ 8 hours battery life (continuous operation)


General Specifications
Operating error
  Refers to the operating temperature range and is guaranteed for 2 years
Storage temp. range
  -20 °C to 60 °C (-4°F to 140 °F)
Reference temp. range
  23 °C ± 5 °C (73 °F ± 9 °F)
Storage humidity
  <75 % Rh
Operating humidity
  <85% Rh
Display
  999 digital LC display with special symbols
Protection
  IP30 according to IEC 529/EN 60529
Safety
  300 V, CAT III pollution degree 2 IEC 61010-1 and IEC 61010-2-032
Weight
  750 g (1.165 lbs)
Conductor size
  35 mm (1.38 in) approximately
Dimension (length x width x depth)
  276 mm x 100 mm x 47 mm (10.8 in x 3.9 in x 1.9 in)
Emission
  IEC 1000 4-2, IEC 61326-I class B
Immunity
  IEC 61000-4-2, 8 kV (air) criteria A
  IEC 61000-4-3, 3 V/m performance criteria A
Range selection
  Auto
Overload indicator
  "OL" on display
Measuring time
  0.5 sec
Measuring frequency
  3.333 kHz
Battery type
  9 V alkaline (type IEC 6 LR 61)
Battery life
  ≥ 8 hours (continuous operation)
Power consumption
  40 mA
Low battery indication
  Display symbol

Ground Loop Resistance (Autorange)
Range
  Accuracy
(± % of reading Ω)
0.025 - 0.250 Ω
  ± 1.5 % rdg ± 0.02 Ω
0.250 - 9.999 Ω
  ± 1.5 % rdg ± 0.05 Ω
10.00 - 99.99 Ω
  ± 2.0 % rdg ± 0.3 Ω
100.0 - 199.9 Ω
  ± 3.0 % rdg ± 1.0 Ω
200.0 - 400.0 Ω
  ± 5.0 % rdg ± 5 Ω
400.0 - 600.0 Ω
  ± 10 % rdg ± 10 Ω
600.0 - 1500 Ω
  ± 20 %